🔌Wire Size Calculator

Enter the load and distance to see the smallest wire that handles both the amps and the voltage drop.

Your circuit

Use at least

10 AWG copper

Ampacity alone: 12 AWG · voltage drop alone: 10 AWG · actual drop 2.5 V (2.1%)

for ampacity

12 AWG

for voltage drop

10 AWG

wire rated amps

30

volts dropped

2.5

Ampacities use the NEC 75°C column with small-conductor limits (14 AWG copper = 15 A, 12 = 20 A, 10 = 30 A). Bundling, heat and conduit fill can require larger wire.

How it works

We check two things and show the larger wire:

  1. Ampacity — from the NEC 75°C ampacity table (with the small-conductor limits: 14 AWG Cu = 15 A, 12 = 20 A, 10 = 30 A).
  2. Voltage drop — VD = 2 × K × amps × one-way feet ÷ circular mils, where K = 12.9 for copper and 21.2 for aluminum. Default limit 3%.

Worked example

20 A at 120 V, 100 ft one-way, copper, 3% max drop (3.6 V):

  • Ampacity alone: 12 AWG
  • 12 AWG drop = 2 × 12.9 × 20 × 100 ÷ 6,530 = 7.9 V — too much
  • 8 AWG drop = 51,600 ÷ 16,510 = 3.1 V ✓ → use 8 AWG

For planning only. Electrical work must follow local code and is best done by a licensed electrician.